There are many types of radiators, including different materials and shapes, as well as different sheet, tube, and water inlet and outlet methods. There are upper inlet and lower outlet, side inlet and side outlet, lower inlet and lower outlet, and bottom inlet and outlet. However, different water inlet and outlet methods have different installation requirements.
There are many types of radiators, including different materials and shapes, as well as different sheet, tube, and water inlet and outlet methods. There are upper inlet and lower outlet, side inlet and side outlet, lower inlet and lower outlet, and bottom inlet and outlet. However, different water inlet and outlet methods have different installation requirements.
1、 Storage and Installation Instructions for Steel Finned Tube Convection Radiator (Vertical Down In Down Out Type)
1. The radiator should be handled with care during transportation to avoid damage, especially to protect the face shield from scratches. Radiators should be stored in ventilated and dry warehouses, classified and arranged according to model and size, with a height not exceeding 1.7 meters. The bottom should be raised by 500px for storage.
2. There are two types of installation methods for vertical radiators: bottom in and bottom out, and top in and top out.
3. Before installing the radiator, the inlet protective material should be removed, and hanging parts should be placed according to the position of the fixing hole. Then, the radiator should be hung, adjusted and tightened, and the face shield should be 125px above the ground.
4. The threads of the radiator are strictly processed and manufactured according to the Ministry of Construction standard J/T6-1999, generally using two types of threads: conical pipe threads or cylindrical pipe threads.
5. Please ensure that the hot water does not exceed the rated working pressure during system experimentation and operation. Steam should not exceed 0.3MPA (gauge pressure) and an automatic pressure reducing valve should be installed.
2、 Storage and installation instructions for steel finned tube convection radiators (side in and side out type)
1. The radiator should be handled with care during transportation to avoid damage, especially to protect the face shield from scratches. Radiators should be stored in ventilated and dry warehouses, classified and arranged according to model and size, with a height not exceeding 1.7 meters. The bottom should be raised by 500px for storage.
2. Side inlet and outlet radiators are divided into three types: same side connection, opposite side connection, and horizontal serial connection.
3. Before installing the radiator, the protective materials at the inlet and outlet should be removed. Hangers should be placed according to the position of the fixing holes, and then the radiator should be hung, adjusted, and tightened. The face shield should be 375px above the ground.
4. The threads of the radiator are strictly processed and manufactured according to the Ministry of Construction standard J/T6-1999, generally using two types of threads: conical pipe threads or cylindrical pipe threads.
5. Please ensure that the hot water does not exceed the rated working pressure during system experimentation and operation. Steam should not exceed 0.3MPA (gauge pressure) and an automatic pressure reducing valve should be installed.
3、 Storage and Installation Instructions for Copper Tube Aluminum Plate Radiator (Vertical Down In Up Out Type)
1. The radiator should be handled with care during transportation to avoid damage, especially to protect the face shield from scratches. Radiators should be stored in ventilated and dry warehouses, classified and arranged according to model and size, with a height not exceeding 1.5 meters. The bottom should be raised by 500px for storage.
2. There are two types of installation methods for vertical radiators: bottom in and bottom out, and top in and top out.
3. Before installing the vertical radiator, the protective materials at the inlet and outlet should be removed. Hangers should be placed according to the position of the fixing holes, and then the radiator should be hung, adjusted and tightened. The face shield should be 125px above the ground.
4. After the installation of the radiator core and before the installation of the face shield, the fins are prone to collapse due to collision and pressure. Please pay attention to protection; If the fins are lodging, please repair them with pointed nose pliers.
5. The threads of the radiator are strictly processed and manufactured according to the Ministry of Construction standard J/T6-1999, generally using two types of threads: conical pipe threads or cylindrical pipe threads.
6. Please ensure that the hot water does not exceed the rated working pressure during system experimentation and operation. Steam should not exceed 0.3MPA (gauge pressure) and an automatic pressure reducing valve should be installed.
4、 Storage and installation instructions for copper tube aluminum sheet heat sink (side in and side out type)
1. The radiator should be handled with care during transportation to avoid damage, especially to protect the face shield from scratches. Radiators should be stored in ventilated and dry warehouses, classified and arranged according to model and size, with a height not exceeding 1.5 meters. The bottom should be raised by 500px for storage.
2. Side inlet and outlet radiators are divided into three types: same side connection, opposite side connection, and horizontal serial connection.
3. Before installing the radiator, the protective materials at the inlet and outlet should be removed. Hangers should be installed according to the fixed hole position, and then the radiator should be hung, adjusted and tightened. The face shield should be 375px above the ground.
4. After the installation of the radiator core and before the installation of the face shield, the fins are prone to collapse due to collision and pressure. Please pay attention to protection; If the fins are lodging, please repair them with pointed nose pliers.
5. The threads of the radiator are strictly processed and manufactured according to the Ministry of Construction standard J/T6-1999, generally using two types of threads: conical pipe threads or cylindrical pipe threads.
6. Please ensure that the hot water does not exceed the rated working pressure during system experimentation and operation. Steam should not exceed 0.3MPA (gauge pressure) and an automatic pressure reducing valve should be installed.
5、 Storage and Installation Instructions for Copper Aluminum Composite Radiators (Vertical Down In Out and Side In Out)
1. The radiator should be handled with care during transportation to avoid damage, especially to protect the sprayed surface from scratches. Radiators should be stored in ventilated and dry warehouses, classified and arranged according to model and size, with a height not exceeding 1.5 meters. The bottom should be raised by 500px for storage.
2. The installation method of copper aluminum composite heat sink can be made into a bottom in and bottom out type and a side in and side out type according to design requirements.
3. Before installing the radiator, the protective materials at the inlet and outlet should be removed. Hangers should be installed according to the position of the fixing holes, and then the radiator should be adjusted and tightened. The radiator should be 625px above the ground.
4. The threads of the radiator are strictly processed and manufactured according to the Ministry of Construction standard J/T6-1999, generally using two types of threads: conical or cylindrical.
5. Please ensure that the hot water does not exceed the rated working pressure during system experimentation and operation. Steam should not exceed 0.3MPA (gauge pressure) and an automatic pressure reducing valve should be installed.
6、 Storage and Installation Instructions for Steel Aluminum Composite Radiators (Vertical Down In Out and Side In Out)
1. The radiator should be handled with care during transportation to avoid damage, especially to protect the sprayed surface from scratches. Radiators should be stored in ventilated and dry warehouses, classified and arranged according to model and size, with a height not exceeding 1.5 meters. The bottom should be raised by 500px for storage.
2. The installation method of the steel aluminum composite radiator can be made into a bottom in and bottom out type and a side in and side out type according to design requirements.
3. Before installing the radiator, the protective materials at the inlet and outlet should be removed. Hangers should be installed according to the position of the fixing holes, and then the radiator should be adjusted and tightened. The radiator should be 625px above the ground.
4. The threads of the radiator are strictly processed and manufactured according to the Ministry of Construction standard J/T6-1999, generally using two types of threads: conical pipe threads or cylindrical pipe threads.
5. Please ensure that the hot water does not exceed the rated working pressure during system experimentation and operation. Steam should not exceed 0.3MPA (gauge pressure) and an automatic pressure reducing valve should be installed.
7、 Storage and Installation Instructions for Steel Column Radiators
1. The radiator should be handled with care during transportation to avoid damage, especially to protect the sprayed surface from scratches. Radiators should be stored in ventilated and dry warehouses, classified and arranged according to model and size, with a height not exceeding 1.5 meters. The bottom should be raised by 500px for storage.
2. The installation methods of steel column radiators are divided into two types: hanging and floor mounted.
3. The threads of the radiator are strictly processed and manufactured according to the Ministry of Construction standard J/T6-1999, generally using two types of threads: conical pipe threads or cylindrical pipe threads.
4. Please ensure that the hot water does not exceed the rated working pressure during system experimentation and operation. Steam should not exceed 0.3MPA (gauge pressure) and an automatic pressure reducing valve should be installed.
8、 Storage and installation instructions for bathroom radiators
1. The radiator should be handled with care during transportation to avoid damage, especially to protect the sprayed surface from scratches. Radiators should be stored in ventilated and dry warehouses, classified and arranged according to model and size, with a height not exceeding 1.5 meters. The bottom should be raised by 500px for storage.
2. Before installing the radiator, the protective materials at the inlet and outlet should be removed. Hangers should be placed according to the position of the fixing holes, and then the radiator should be hung, adjusted, and tightened.
3. The threads of the radiator are strictly processed and manufactured according to the Ministry of Construction standard J/T6-1999, generally using two types of threads: conical pipe threads or cylindrical pipe threads.
4. Please ensure that the hot water does not exceed the rated working pressure during system experimentation and operation. Steam should not exceed 0.3MPA (gauge pressure) and an automatic pressure reducing valve should be installed.
9、 Storage and Installation Instructions for Steel Flat Tube Radiators
1. The radiator should be handled with care during transportation to avoid damage, especially to protect the sprayed surface from scratches. Radiators should be stored in ventilated and dry warehouses, classified and arranged according to model and size, with a height not exceeding 1.5 meters. The bottom should be raised by 500px for storage.
2. Before installing the radiator, the protective materials at the inlet and outlet should be removed. Hangers should be placed according to the position of the fixing holes, and then the radiator should be hung, adjusted, and tightened.
3. The threads of the radiator are strictly processed and manufactured according to the Ministry of Construction standard J/T6-1999, generally using two types of threads: conical pipe threads or cylindrical pipe threads.
4. Please ensure that the hot water does not exceed the rated working pressure during system experimentation and operation. Steam should not exceed 0.3MPA (gauge pressure) and an automatic pressure reducing valve should be installed.
10、 Storage and installation instructions for steel series (closed) radiators
1. The radiator should be handled with care during transportation to avoid damage, especially to protect the sprayed surface from scratches. Radiators should be stored in ventilated and dry warehouses, classified and arranged according to model and size, with a height not exceeding 1.5 meters. The bottom should be raised by 500px for storage.
2. Before installing the radiator, the protective materials at the inlet and outlet should be removed. Hangers should be placed according to the position of the fixing holes, and then the radiator should be hung, adjusted, and tightened.
3. The threads of the radiator are strictly processed and manufactured according to the Ministry of Construction standard J/T6-1999, generally using two types of threads: conical pipe threads or cylindrical pipe threads.
4. Please ensure that the hot water does not exceed the rated working pressure during system experimentation and operation. Steam should not exceed 0.3MPA (gauge pressure) and an automatic pressure reducing valve should be installed.
11、 Storage and Installation Instructions for Steel Arc Tube Radiators
1. The radiator should be handled with care during transportation to avoid damage, especially to protect the sprayed surface from scratches. Radiators should be stored in ventilated and dry warehouses, classified and arranged according to model and size, with a height not exceeding 1.5 meters. The bottom should be raised by 500px for storage.
2. Before installing the radiator, the protective materials at the inlet and outlet should be removed. Hangers should be placed according to the position of the fixing holes, and then the radiator should be hung, adjusted, and tightened.
3. The threads of the radiator are strictly processed and manufactured according to the Ministry of Construction standard J/T6-1999, generally using two types of threads: conical pipe threads or cylindrical pipe threads.
4. Please ensure that the hot water does not exceed the rated working pressure during system experimentation and operation. Steam should not exceed 0.3MPA (gauge pressure) and an automatic pressure reducing valve should be installed.